Single Compartment Ducts

Single compartment ducts are the channelized elements of the system, consisting of a single compartment through which the smoke passage occurs.


COND-S - Single Compartment Smoke Control Ducts

Description

COND-S ducts are used in Single Compartment Smoke and Heat Exhaust Systems, where smoke is extracted from a single fire compartment before reaching the outside of the building. These ducts can include straight sections, connecting components, and special pieces.
The SEFFC FUMOVENT® system is equipped with a FUMOCONTROL system for balancing and regulating smoke extraction through the various openings located on the ducts as designed.


Reference Standards

COND-S ducts are CE marked according to UNI EN 12101-7:2011 under EU Regulation 305/2011 and tested according to EN 1366-9:2008.


Classification

  • E600 120(Ho) S 500 / 1500 mono
  • Resistant to 600°C for 120 minutes
  • Cold smoke tightness class S for an operating pressure of -1500/+500 Pa

COND-SB - Single Compartment Smoke Control Ducts (Big Size)

Description

COND-SB ducts are used in Single Compartment Smoke and Heat Exhaust Systems, where smoke is extracted from a single fire compartment before reaching the outside of the building. These ducts can include straight sections, connecting components, and special pieces, with maximum dimensions up to 2000x1500 mm.
The SEFFC FUMOVENT system is equipped with a FUMOCONTROL system for balancing and regulating smoke extraction through the various openings located on the ducts as designed.


Reference Standards

COND-SB ducts are CE marked according to UNI EN 12101-7:2011 under EU Regulation 305/2011 and tested according to EN 1366-9:2008.


Classification

  • E600 120(Ho) S 500 / 1500 mono
  • Resistant to 600°C for 120 minutes
  • Cold smoke tightness (S) for an operational pressure of -1500/+500 Pa

Micro-Perforated Duct for HVAC and SEFFC

Description

Perforated duct designed for HVAC systems (Heating, Ventilation, and Air Conditioning), certified for use in smoke extraction systems SEFFC (Smoke and Fire Extraction Forced Ventilation Systems) - UNI 9494-2.


Reference Standards

Air handling and spare parts UNI 10339; Smoke Disposal and Extraction in case of fire UNI 9494-2.


Classification

  • E600 120(Ho) S 1000 mono
  • Resistant to 600°C for 120 minutes
  • Cold smoke tightness (S) for an operational pressure of 500 1000 Pa