Galvanized steel grilles for rectangular ducts, used in smoke and heat evacuation systems (SEFFC) and for natural air intake. They are suitable for single-compartment smoke control and can be painted in RAL colors upon request.
The GRID-M grilles are CE marked according to UNI EN 12101-7:2011 regulations under the EU Regulation 305/2011 and tested according to EN 1366-9:2008.
E600 120 (Ho) S 500 / 1500 mono
Resistant to 600°C for 120 minutes
Cold smoke tightness S for an operating pressure of -1500/+500 Pa
Finned galvanized steel grille for rectangular ducts, used for natural air intake. Suitable for single-compartment smoke control and can be painted in RAL colors upon request.
The GRID-M-AL grilles comply with UNI 9494-2 regulations and are free of plastic parts. They are sized for air intake at 1m/s or 2m/s.
The FUMOCONTROL system (Patented System) allows for the regulation of air flows and volumes in SEFFC systems to enable correct adjustment and easy system setup on-site by the installer.
This system ensures that there is adequate smoke extraction at the final outlets of the systems, achieved through the balancing of flow rates at the initial outlets, where there is normally higher suction.
The system consists of control panels that manage dampers and extractors to adjust the flow in branches, along with specialized software to establish the percentage of opening for a plurality of outlets on branches and to preconfigure each numbered outlet on every duct for installation on-site.
The adjustable B-CONTROL outlets can be used for extraction or intake purposes.
They can be installed directly on ducts with minimal space compared to traditional adjustable grilles or mounted on a false ceiling, made of galvanized steel, and can be painted in RAL colours upon request.
The adjustable B_CONTROL outlets for smoke extraction ducts are CE marked according to UNI EN 12101-7:2011 regulations under EU Regulation 305/2011 and tested according to EN 1366-9:2008.
E600 120 (Ho) S 500 / 1500 mono
Resistant to 600°C for 120 minutes
Cold smoke tightness S for an operating pressure of -1500/+500 Pa