h-header

pagina-dinamica

banner

breadcrumb

Command and Control Centers


Command and control centers are the core of the FUMO VENT system. Managed by dedicated software, they activate system automations and verify environmental conditions.


QE Puls - Control Panel for Fire Brigade (VVF) and Emergency Teams


Reference Standards

  • UNI 9494-2
  • EN 54-13

Description

QE-PULS is an electrical control panel for the extraction/intake fans, dampers, and related equipment within the SEFFC system field. It includes a dedicated control interface for the Fire Brigade (VVF) to switch the FUMO VENT® system between Automatic and Manual modes, as well as the ability to remotely activate and deactivate extractors from a safe zone.
The panel can be equipped with an LED panel displaying the SEFFC system layout.


Features

Made of painted steel, with approximate dimensions of 800x800x400mm, containing:

  • Protection switches
  • Control and emergency buttons on the panel
  • 1 general selector switch Man/AUT (with KEY), exclusively controlled by the Fire Brigade (VVF)
  • Dual Start/Stop buttons for extractor control
  • Green LEDs indicating extractor operational status
  • Red LEDs indicating extractor non-operational status
  • LEDs indicating manual/automatic mode status
  • Red LED indicating alarm status
  • Synoptic panel screen-printed on the front of the panel, showing the system layout
  • Interface relay + BUS card + Loop cards

QE Fire Mode - Power Panel with Inverter for Extractor Startup

Description

QE-FIRE MODE is an electrical panel equipped with an inverter designed for FIRE MODE operation at 400Vac, suitable for reversible extractors.


Features

It can be equipped with I/O control cards connected to the SEFFC system loop at the SF3000 central control.


Reference Standards

  • UNI 9494-2
  • EN 12101-3

CE Marking Conforms to the Following Standards:

  • RoHS II Directive 2011/65/EC
  • WEEE Directive 2012/19/EU
  • European Directive 2014/35/EU
  • Electromagnetic Compatibility 2014/30/EU and subsequent amendments, compliant with the following technical standards:
    • EN 61439-1
    • EN 61000-3-2
    • EN 61000-3-3
    • EN 61000-6-1
    • EN 61000-6-2
    • EN 60204-1

Classification

  • E600 120(Ho) S 500 / 1500 mono
  • Resistant to 600°C for 120 minutes
  • Cold smoke tightness (S) for an operational pressure of -1500/+500 Pa

QE ST - Power Panel for Star-Delta Starting of SEFFC Extractors

Description

QE-ST is an electrical panel designed for star-delta starting of extractors at 400Vac.


Key Features

  • Power Supply: 3-phase, 50/60Hz, 400V±10%
  • Inputs and control circuits at low voltage
  • Voltage presence contact
  • Thermal release contact (for signaling purposes only)
  • Extractor started contact
  • IP54 enclosure
  • Ambient temperature: -5/+40 °C

Optional Features

  • Programmable timers for timed operation (e.g., room cleaning/CO garage cleaning).
  • Motor alternation relays.
  • Can be equipped with I/O control cards connected to the SEFFC system loop at the SF3000 central control.

Reference Standards

  • UNI 9494-2
  • EN 12101-3

CE Marking Conforms to the Following Standards:

  • RoHS II Directive 2011/65/EC
  • WEEE Directive 2012/19/EU
  • European Directive 2014/35/EU
  • Electromagnetic Compatibility 2014/30/EU and subsequent amendments, compliant with the following technical standards:
    • EN 61439-1
    • EN 61000-3-2
    • EN 61000-3-3
    • EN 61000-6-1
    • EN 61000-6-2
    • EN 60204-1

QE Directo - Power Panel for Direct Starting of SEFFC Extractors

Description

QE-DIRECTO is an electrical panel designed for direct starting of extractors at 400Vac.


Key Features

  • Power Supply: 3-phase, 50/60Hz, 400V±10%
  • Inputs and control circuits at low voltage
  • Voltage presence contact
  • Thermal release contact (for signaling purposes only)
  • Extractor started contact
  • IP54 enclosure
  • Ambient temperature: -5/+40 °C

Optional Features

  • Ability to start up to 10 extractors with a single panel.
  • Programmable timers for timed operation (e.g., room cleaning/CO garage cleaning).
  • Motor alternation relays.
  • Can be equipped with I/O control cards connected to the SEFFC system loop at the SF3000 central control.

Reference Standards

  • UNI 9494-2
  • EN 12101-3

CE Marking Conforms to the Following Standards:

  • RoHS II Directive 2011/65/EC
  • WEEE Directive 2012/19/EU
  • European Directive 2014/35/EU
  • Electromagnetic Compatibility 2014/30/EU and subsequent amendments, compliant with the following technical standards:
    • EN 61439-1
    • EN 61000-3-2
    • EN 61000-3-3
    • EN 61000-6-1
    • EN 61000-6-2
    • EN 60204-1

SF-3000 - Central Management Unit with Redundant Technology for SEFFC Systems

Description

For large-scale smoke extraction systems with numerous scenarios and components in the field, the optimal solution for management is the FUMOVENT SF 3000 Central Unit. This central unit is specifically designed to handle countless complex scenarios and features redundant technology.
In the event of a failure of the control boards in the central unit, the system can continue to operate seamlessly with the assistance of fully redundant electronics.
This ensures that SEFFC FUMOVENT systems achieve very high reliability compared to traditional systems available on the market.


Reference Standards

  • EN 54-13
  • UNI 9494-2

SF-500 - Central Management Unit for SEFFC Smoke Extraction Systems

Description

The SEFFC system is managed by the SF500 control panel and field control modules according to UNI 9494-2 regulations.
The SF 500 control panel (up to 60 modules) with 1500 meters of loop capacity:
This FUMOVENT panel is capable of switching the SEFFC system from a standby state to a fire state based on programmed scenarios, controlling, moving, and indicating the status of all active elements of the system.
Designed in compliance with current regulations, including EN54 and Vds Approval.
The panel can activate multiple zones simultaneously.
It can interface with and control various active components of the line through FUMOVENT BX field modules for the correct operation of system scenarios.
Communication protocol is Modbus RTU (RS-485) or BACnet (MS/TP), with automatic recognition of IP addresses of connected devices.
Features a color screen and programming to manage multiple fire scenarios and monitor up to 250 addresses (63 components of the SEFFC system). The system supports loops ranging from 3500 meters (with over 30 cards) to 1500 meters.


Reference Standards

  • UNI 9494-2
  • EN 54-13

QE - Control and Command Panels

Description

QE electrical panels are designed for controlling extraction/intake fans, dampers, and field equipment within the SEFFC (Smoke and Fire Extraction Forced Ventilation) system. These panels can manage the entire SEFFC system with numerous logics and programming capabilities, interfacing with all components of the FUMOVENT® range.
Forced smoke and heat extraction systems may include extractors, air supply units, field dampers, mobile smoke barriers, and interfaces with IRAI and HVAC systems. Therefore, according to UNI 9494-2 regulations, it's essential that the system architecture is managed by a single control center. QE panels are custom-designed, tested, and installed for this purpose.


Reference Standards

  • Compliance with EN54-13; EN 61439-1/3, CEI 17-43, CEI 64-8, CEI EN 60204-1
  • Legislative Decree no. 81/08: "Assembled protection and control devices for low voltage"
  • Electrical wiring compliant with EU Directives 2006/95/CE, 2004/108/CE, 92/31 CEE, and subsequent amendments
  • Modular approach for EMC directive
  • Interfaceability with fire control and command panels UNI 9795

QALI - Power Supply Panel 230/24V dc

Description

QALI is an electrical panel complete with a certified power supply for SEFFC (Smoke and Fire Extraction Forced Ventilation) systems - EN12101-10.

  • Power supply: 230V AC
  • Connection board to the SF3000 system interface
  • Voltage presence contact
  • Fault contact
  • IP44 enclosure

Optional Features

Can be equipped with I/O control cards connected to the SEFFC system loop at the SF3000 central control.


Reference Standards

QALI power supply panels are CE marked according to UNI EN 12101-10 in accordance with EU Regulation 305/2011.


BX 0214-HP - Actuator Control Board for Smoke Control Dampers up to 8A

Description

The BX 0214-HP is a universal module capable of controlling and monitoring 1 or 2 smoke control dampers from the FUMO-VENT series and/or fire control dampers.
This module is designed in compliance with fire safety standards and regulations. It conforms to UNI EN54 and is suitable for "Smoke and Heat Control Systems - Part 2: Design and Installation of Smoke and Heat Exhaust Systems (SEFFC)."

  • Ability to monitor the status of the damper (OPEN/CLOSED)
  • Ability to perform operational tests directly on the damper remotely at any time.

The board is designed to activate damper actuators in the field with peak currents up to 8A.


Terminal connections

  • X1: Monitored Input
  • X2: Relay 1-2
  • X5: Loop

Reference Standards

  • CE Marking compliant with the following standards:
  • EN54-13 (the system is fully certified for fire safety)
  • Electromagnetic Compatibility 2014/30/EU and subsequent amendments
  • EN 61439-1; EN 61000-3-2; EN 61000-3-3; EN 61000-6-1; EN 61000-6-2; EN 60204-1.

B-FLOW - Power Panel for Controlling the Extracted Flow Rate in SEFFC System, with Flow Meter on the Circuit

Description

B-FLOW is a flow meter (measuring in cubic meters per hour, mc/h) interfaced with the QE FIRE MODE panel. The flow meter will be installed on the smoke extraction duct either before or after the extractor in a straight section.

  • Maximum temperature: 450°C
  • Duct size: 1000x1000
  • Suitable for air with soot
  • Maximum flow rate: 108,000 Nm3/h
  • Maximum speed: 30 Nm/s
  • IP65 rating
  • Pressure: 1.6 MPa
  • 4-20mA – RS485

Reference Standards

  • RoHS II Directive 2011/65/EC
  • WEEE Directive 2012/19/UE
  • European Directive 2014/35/EU
  • Electromagnetic Compatibility 2014/30/EU and subsequent amendments, compliant with the following technical standards:
    • EN 61439-1
    • EN 61000-3-2
    • EN 61000-3-3
    • EN 61000-6-1
    • EN 61000-6-2
    • EN 60204-1
related-links

h-footer